Show filters
2 Total Results
Displaying 1-2 of 2
Sort by:
Attacker Value
Unknown

CVE-2022-30262

Disclosure Date: August 17, 2022 (last updated October 08, 2023)
The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks.
Attacker Value
Unknown

CVE-2018-5452

Disclosure Date: March 07, 2018 (last updated November 26, 2024)
A Stack-based Buffer Overflow issue was discovered in Emerson Process Management ControlWave Micro Process Automation Controller: ControlWave Micro [ProConOS v.4.01.280] firmware: CWM v.05.78.00 and prior. A stack-based buffer overflow vulnerability caused by sending crafted packets on Port 20547 could force the PLC to change its state into halt mode.