Show filters
20 Total Results
Displaying 1-10 of 20
Sort by:
Attacker Value
Very High
CVE-2021-22779
Disclosure Date: July 14, 2021 (last updated November 28, 2024)
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
1
Attacker Value
Unknown
CVE-2025-0327
Disclosure Date: February 13, 2025 (last updated February 13, 2025)
CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit
trail data and the other acting as server managing client request) that could cause a loss of Confidentiality,
Integrity and Availability of engineering workstation when an attacker with standard privilege modifies the
executable path of the windows services. To be exploited, services need to be restarted.
0
Attacker Value
Unknown
CVE-2024-10083
Disclosure Date: February 13, 2025 (last updated February 13, 2025)
CWE-20: Improper Input Validation vulnerability exists that could cause denial of service of engineering
workstation when specific driver interface is invoked locally by an authenticated user with crafted input.
0
Attacker Value
Unknown
CVE-2023-6409
Disclosure Date: February 14, 2024 (last updated December 21, 2024)
CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized
access to a project file protected with application password when opening the file with
EcoStruxure Control Expert.
0
Attacker Value
Unknown
CVE-2023-6408
Disclosure Date: February 14, 2024 (last updated January 24, 2025)
CWE-924: Improper Enforcement of Message Integrity During Transmission in a
Communication Channel vulnerability exists that could cause a denial of service and loss of
confidentiality, integrity of controllers when conducting a Man in the Middle attack.
0
Attacker Value
Unknown
CVE-2023-27975
Disclosure Date: February 14, 2024 (last updated December 21, 2024)
CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause unauthorized
access to the project file in EcoStruxure Control Expert when a local user tampers with the
memory of the engineering workstation.
0
Attacker Value
Unknown
CVE-2022-45789
Disclosure Date: January 31, 2023 (last updated October 08, 2023)
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions)
0
Attacker Value
Unknown
CVE-2022-45788
Disclosure Date: January 30, 2023 (last updated October 08, 2023)
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions)
0
Attacker Value
Unknown
CVE-2022-37300
Disclosure Date: September 12, 2022 (last updated October 08, 2023)
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).
0
Attacker Value
Unknown
CVE-2022-26507
Disclosure Date: April 14, 2022 (last updated November 08, 2023)
A heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7. A crafted input file can lead to remote code execution. This is not the same as any of: CVE-2021-21810, CVE-2021-21811, CVE-2021-21812, CVE-2021-21815, CVE-2021-21825, CVE-2021-21826, CVE-2021-21828, CVE-2021-21829, or CVE-2021-21830. NOTE: This vulnerability only affects products that are no longer supported by the maintainer
0