Attacker Value
Unknown
(0 users assessed)
Exploitability
Unknown
(0 users assessed)
User Interaction
None
Privileges Required
None
Attack Vector
Network
0

CVE-2017-7574

Disclosure Date: April 06, 2017
Add MITRE ATT&CK tactics and techniques that apply to this CVE.

Description

Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.

Add Assessment

No one has assessed this topic. Be the first to add your voice to the community.

CVSS V3 Severity and Metrics
Base Score:
9.8 Critical
Impact Score:
5.9
Exploitability Score:
3.9
Vector:
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Attack Vector (AV):
Network
Attack Complexity (AC):
Low
Privileges Required (PR):
None
User Interaction (UI):
None
Scope (S):
Unchanged
Confidentiality (C):
High
Integrity (I):
High
Availability (A):
High

General Information

Additional Info

Technical Analysis