Show filters
1 Total Results
Displaying 1-1 of 1
Sort by:
Attacker Value
Unknown

CVE-2022-30316

Disclosure Date: July 28, 2022 (last updated October 08, 2023)
Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded cre…