Unknown

CVE-2022-3353

Disclosure Date: February 21, 2023 (last updated November 08, 2023)
A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products.  An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting new MMS-client connections.  Already existing/established client-server connections are not affected. List of affected CPEs: * cpe:2.3:o:hitachienergy:fox61x_tego1:r15b08:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16_3:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1e01:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1d02:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1c07:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1b02:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:gms600:1.3.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.1.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachien…
Attacker Value
Unknown

CVE-2021-40333

Disclosure Date: November 23, 2021 (last updated February 23, 2025)
Weak Password Requirements vulnerability in Hitachi Energy FOX61x, XCM20 allows an attacker to gain unauthorized access to the Data Communication Network (DCN) routing configuration. This issue affects: Hitachi Energy FOX61x versions prior to R15A. Hitachi Energy XCM20 versions prior to R15A.
Attacker Value
Unknown

CVE-2021-40334

Disclosure Date: November 23, 2021 (last updated February 23, 2025)
Missing Handler vulnerability in the proprietary management protocol (port TCP 5558) of Hitachi Energy FOX61x, XCM20 allows an attacker that exploits the vulnerability by activating SSH on port TCP 5558 to cause disruption to the NMS and NE communication. This issue affects: Hitachi Energy FOX61x versions prior to R15A. Hitachi Energy XCM20 versions prior to R15A.
Attacker Value
Unknown

CVE-2021-27196

Disclosure Date: March 15, 2021 (last updated February 22, 2025)
Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3…