CVE-2022-33174

Disclosure Date: June 13, 2022
Add MITRE ATT&CK tactics and techniques that apply to this CVE.

Description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

Add Assessment

No one has assessed this topic. Be the first to add your voice to the community.

CVSS V3 Severity and Metrics
Base Score:
7.5 High
Impact Score:
3.6
Exploitability Score:
3.9
Vector:
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Attack Vector (AV):
Network
Attack Complexity (AC):
Low
Privileges Required (PR):
None
User Interaction (UI):
None
Scope (S):
Unchanged
Confidentiality (C):
High
Integrity (I):
None
Availability (A):
None