Unknown

CVE-2021-22681

Disclosure Date: March 03, 2021 (last updated February 22, 2025)
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
Attacker Value
Unknown

CVE-2016-9343

Disclosure Date: February 13, 2017 (last updated November 26, 2024)
An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service.
Attacker Value
Unknown

CVE-2014-0755

Disclosure Date: February 05, 2014 (last updated October 05, 2023)
Rockwell Automation RSLogix 5000 7 through 20.01, and 21.0, does not properly implement password protection for .ACD files (aka project files), which allows local users to obtain sensitive information or modify data via unspecified vectors.
0
Attacker Value
Unknown

CVE-2012-0222

Disclosure Date: April 02, 2012 (last updated October 04, 2023)
The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 allows remote attackers to cause a denial of service (out-of-bounds read) via a crafted packet.
0
Attacker Value
Unknown

CVE-2012-0221

Disclosure Date: April 02, 2012 (last updated October 04, 2023)
The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 does not properly handle the return value from an unspecified function, which allows remote attackers to cause a denial of service (service outage) via a crafted packet.