Show filters
6 Total Results
Displaying 1-6 of 6
Sort by:
Attacker Value
Unknown

CVE-2024-21916

Disclosure Date: January 31, 2024 (last updated February 08, 2024)
A denial-of-service vulnerability exists in specific Rockwell Automation ControlLogix ang GuardLogix controllers. If exploited, the product could potentially experience a major nonrecoverable fault (MNRF). The device will restart itself to recover from the MNRF.
Attacker Value
Unknown

CVE-2022-3157

Disclosure Date: December 16, 2022 (last updated November 08, 2023)
A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).
Attacker Value
Unknown

CVE-2020-6998

Disclosure Date: July 27, 2022 (last updated October 07, 2023)
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.
Attacker Value
Unknown

CVE-2022-1797

Disclosure Date: June 02, 2022 (last updated October 07, 2023)
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.
Attacker Value
Unknown

CVE-2022-1161

Disclosure Date: March 31, 2022 (last updated October 07, 2023)
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
Attacker Value
Unknown

CVE-2016-9343

Disclosure Date: February 13, 2017 (last updated November 26, 2024)
An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service.