CVE-2021-32984
Disclosure Date: April 04, 2022 (last updated February 23, 2025)
All programming connections receive the same unlocked privileges, which can result in a privilege escalation. During the time Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, an attacker can connect to the PLC and read the project without authorization.
0
Attacker Value
Unknown
CVE-2021-32982
Disclosure Date: April 04, 2022 (last updated February 23, 2025)
Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 passwords are sent as plaintext during unlocking and project transfers. An attacker who has network visibility can observe the password exchange.
0
Attacker Value
Unknown
CVE-2021-32980
Disclosure Date: April 04, 2022 (last updated February 23, 2025)
Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 does not protect against additional software programming connections. An attacker can connect to the PLC while an existing connection is already active.
0
Attacker Value
Unknown
CVE-2021-32978
Disclosure Date: April 04, 2022 (last updated February 23, 2025)
The programming protocol allows for a previously entered password and lock state to be read by an attacker. If the previously entered password was successful, the attacker can then use the password to unlock Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00.
0
Attacker Value
Unknown
CVE-2020-10922
Disclosure Date: July 23, 2020 (last updated February 21, 2025)
This vulnerability allows remote attackers to create a denial-of-service condition on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the EA-HTTP.exe process. The issue results from the lack of proper input validation prior to further processing user requests. An attacker can leverage this vulnerability to create a denial-of-service condition on the system. Was ZDI-CAN-10527.
0
Attacker Value
Unknown
CVE-2020-10921
Disclosure Date: July 23, 2020 (last updated February 21, 2025)
This vulnerability allows remote attackers to issue commands on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the EA-HTTP.exe process. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to issue commands to the physical equipment controlled by the device. Was ZDI-CAN-10482.
0
Attacker Value
Unknown
CVE-2020-10918
Disclosure Date: July 23, 2020 (last updated February 21, 2025)
This vulnerability allows remote attackers to bypass authentication on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the authentication mechanism. The issue is due to insufficient authentication on post-authentication requests. An attacker can leverage this vulnerability to escalate privileges to resources normally protected from unauthenticated users. Was ZDI-CAN-10182.
0
Attacker Value
Unknown
CVE-2020-10920
Disclosure Date: July 23, 2020 (last updated February 21, 2025)
This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the control service, which listens on TCP port 9999 by default. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to execute code in the context of the device. Was ZDI-CAN-10493.
0
Attacker Value
Unknown
CVE-2020-10919
Disclosure Date: July 23, 2020 (last updated February 21, 2025)
This vulnerability allows remote attackers to disclose sensitive information on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of passwords. When transmitting passwords, the process encrypts them in a recoverable format. An attacker can leverage this vulnerability to disclose credentials, leading to further compromise. Was ZDI-CAN-10185.
0
Attacker Value
Unknown
CVE-2020-6969
Disclosure Date: February 05, 2020 (last updated February 21, 2025)
It is possible to unmask credentials and other sensitive information on “unprotected” project files, which may allow an attacker to remotely access the C-More Touch Panels EA9 series: firmware versions prior to 6.53 and manipulate system configurations.