Show filters
46 Total Results
Displaying 11-20 of 46
Sort by:
Attacker Value
Unknown

CVE-2020-6990

Disclosure Date: March 16, 2020 (last updated February 21, 2025)
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller.
Attacker Value
Unknown

CVE-2019-10955

Disclosure Date: April 25, 2019 (last updated November 27, 2024)
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a malicious site that could run or download arbitrary malware on the user’s machine.
0
Attacker Value
Unknown

CVE-2018-17924

Disclosure Date: December 07, 2018 (last updated November 27, 2024)
Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules An unauthenticated, remote threat actor could send a CIP connection request to an affected device, and upon successful connection, send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration, a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address.
Attacker Value
Unknown

CVE-2017-12092

Disclosure Date: June 04, 2018 (last updated November 26, 2024)
An exploitable file write vulnerability exists in the memory module functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a file write resulting in a new program being written to the memory module. An attacker can send an unauthenticated packet to trigger this vulnerability.
0
Attacker Value
Unknown

CVE-2017-14468

Disclosure Date: April 05, 2018 (last updated November 26, 2024)
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: This ability is leveraged in a larger exploit to flash custom firmware.
Attacker Value
Unknown

CVE-2017-12093

Disclosure Date: April 05, 2018 (last updated November 26, 2024)
An exploitable insufficient resource pool vulnerability exists in the session communication functionality of Allen Bradley Micrologix 1400 Series B Firmware 21.2 and before. A specially crafted stream of packets can cause a flood of the session resource pool resulting in legitimate connections to the PLC being disconnected. An attacker can send unauthenticated packets to trigger this vulnerability.
Attacker Value
Unknown

CVE-2017-14470

Disclosure Date: April 05, 2018 (last updated November 26, 2024)
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.
0
Attacker Value
Unknown

CVE-2017-14471

Disclosure Date: April 05, 2018 (last updated November 26, 2024)
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.
0
Attacker Value
Unknown

CVE-2017-12088

Disclosure Date: April 05, 2018 (last updated November 26, 2024)
An exploitable denial of service vulnerability exists in the Ethernet functionality of the Allen Bradley Micrologix 1400 Series B FRN 21.2 and below. A specially crafted packet can cause a device power cycle resulting in a fault state and deletion of ladder logic. An attacker can send one unauthenticated packet to trigger this vulnerability
0
Attacker Value
Unknown

CVE-2017-14469

Disclosure Date: April 05, 2018 (last updated November 26, 2024)
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0028 Fault Type: Non-User Description: Values 0x01 and 0x02 are invalid values for the user fault routine. By writing directly to the file it is possible to set these values. When this is done and the device is moved into a run state, a fault is triggered. NOTE: This is not possible through RSLogix.
0